STRIPING : From the point the fire lane begins to the point the fire lane ends, including behind all parking spaces which adjoin a fire lane, there shall be painted one continuous red stripe having a minimum width of at least six inches (6"). Fire lanes shall be stenciled every twenty-five feet (25') apart "NO PARKING FIRE LANE" with white lettering four inches (4") high and at least one half-inch ( 1/2") stroke. Fire lanes shall be so marked on both sides of the lane.
SIGNAGE (When approved): Signs that comply with IFC Section D103.6 shall be mounted conspicuously along the edge of the fire lane, spaced no more than twenty-five feet (25') apart, and shall have lettering at least two inches (2") high with three-eighths inch (3/8") stroke.